Bill of Materials

BOM — Electrical

Electrical bill of materials: sub-panel, circuits, outlets, data cabling, and acoustic wiring rules. Star topology grounding with isolated ground conductors.

Sub-Panel Specification

Type
DIN-rail dedicated studio zone panel
Supply
240V / 50Hz single-phase
Main MCB
32A
Grounding
Star topology, single technical earth, TN-S
IG conductors: Dedicated isolated ground per circuit — orange receptacles throughout.

Circuit Schedule

CircuitRoomBreakerLoadUtilizationReceptacle
AV-01Control Room B31116A MCB480W13%Schuko IG orange
AV-02VO Live B30416A MCB385W10%Schuko IG orange
AV-03Video Studio B312-116A MCB1,160W30%Schuko IG orange
AV-04Editing Suite B312-216A MCB1,950W51%Schuko IG orange
TOTAL3,975W52%32A main

Outlet Position Schedule

IDRoomWallHeight AFFCircuitNotes
CR-P1ControlSouth45cmAV-01Interface + monitors
CR-FBControlFloor boxAV-012× Schuko + 2× Cat6A
VO-P1VO LiveNorth45cmAV-02General
VO-P2VO LiveEast45cmAV-02General
VO-P3VO LiveEast150cmAV-02Dubbing monitors
ST-P1StudioNorth45cmAV-03Camera / teleprompter
ST-P2StudioEast45cmAV-03LED array
ST-GSStudioEast265cmAV-03GREEN SCREEN — critical height
ST-FBStudioFloor boxAV-03Power + data combo
ED-P1EditingSouth45cmAV-04Workstation 1
ED-P2EditingSouth45cmAV-04Workstation 2
ED-P3EditingSouth45cmAV-04Workstation 3
ED-P4EditingEast45cmAV-04NAS

Data Cabling Schedule

IDRoomWallHeightTypeNotes
CR-D1ControlSouth45cmCat6A S/FTPDante network
CR-D2ControlEast45cmCat6A S/FTPLAN
ST-AFB1StudioFloor box8× XLR audioB306 confirmed
ST-AFB2StudioFloor box8× XLR audioB306 confirmed
ED-D1EditingSouth45cmCat6A S/FTPWorkstation 1
ED-D2EditingSouth45cmCat6A S/FTPWorkstation 2
ED-D3EditingSouth45cmCat6A S/FTPWorkstation 3
ED-D4EditingEast45cmCat6A S/FTPNAS direct
Patch Panel
12-port Cat6A, rack-mounted in Editing Suite

Acoustic Wiring Rules [AC]

RuleSpecificationReason
No back-to-back boxesMinimum 600mm horizontal offset across STC-rated partitionsDirect sound path through wall
Putty padsOSI SpecSeal or equivalent behind EVERY box in STC wallsFire + acoustic seal
Box materialSteel boxes ONLY in STC walls — NO plasticPlastic flexes, breaks seal
Conduit25mm EMT steel, 300mm from audio signal conduitEMI/RFI separation
Crossings90° crossings ONLY where power and signal must crossMinimize coupling
Audio cableMinimum CM rated, Mogami W2534 for balanced runsFire rating + shielding

Grounding & IG Components [AC]

ItemQtySpecification
Isolated ground bus bar1At sub-panel — single star ground point for all AV circuits [AC]
IG receptacles (orange Schuko 16A)12 est.All AV circuit outlets — isolated ground type. CR-P1/P2, VO-P1/P2/P3, ST-P1/P2, ED-P1/P2/P3/P4 + floor boxes
IG conductor (green/yellow insulated)Per runSeparate insulated conductor in each conduit — NOT bonded to EMT conduit