HVAC Bill of Materials

Complete HVAC equipment and silencer specifications · SSOT v3.7 · Audience: MEP contractor, procurement

AC Acoustic Critical HP Hold Point — stop work, obtain sign-off

System Overview

System: Daikin VRF (Variable Refrigerant Flow) — NOT Samsung. 3× indoor units, 1× outdoor unit. 8 fresh air terminals (2 per room).

Indoor Unit Schedule

Unit IDRoom servedTypeLocationNC targetNotes
IDU-04VO LiveDedicatedNorth wallNC-12 maxAC
IDU-03Control + EditingSharedNorth wallNC-18 max
IDU-05Video StudioDedicatedNorth wallNC-18 max
ODUOutdoor unitCompressor/condenserSouth sideDaikin VRF

Silencer Schedule

All 5 silencer runs are independent — B1 and B2 are never collapsed. Trunk B crosstalk = B1+B2 combined = 25dB only.
Action required: Install 15-20dB inline silencer on Run B2 (Editing Suite branch) before commissioning. This is a HOLD POINT HP — do not commission without silencer verified on B2 branch.
RunServesLengthAttenuationMax velocityNC limit
AVO Live1500 mm40 dB1.5 m/sNC-12 AC
BControl+Editing trunk1000 mm25 dB2.5 m/sNC-18
B1Control branch500 mm15 dB2.0 m/sNC-18
B2Editing branch300 mm10 dB2.5 m/sNC-25
CVideo Studio1000 mm25 dB2.0 m/sNC-18

Duct Accessories

ItemSpecNotes
Flexible canvas connectorsBoth ends of every silencerAC
Duct hangersNeoprene-isolated · every 600mm
Fresh air terminals8 total · 2 per room

Vibration Isolation Materials

ItemSpecNotes
IDU anti-vibration mountsSpring/neoprene isolators · 25mm min deflectionAC
Duct hanger isolatorsNeoprene pads · every 600mm
Flexible connectorsCanvas flexible duct connectorsBoth ends of every silencer AC

NC Performance Targets

RoomNC targetCritical
VO LiveNC-12AC Lowest — highest sensitivity mic use
Control RoomNC-18
Video StudioNC-18
Editing SuiteNC-25

Hold Points

HPDescription
HP 6.0Acoustic consultant approves silencer submittals before ordering
HP 6.1Velocity and attenuation verified in situ before closing walls