NC curves define maximum allowable noise levels per octave band. All measurements with HVAC running at normal operation.

Note: Values shown are the NC curve octave-band pressure limits. Room NC tables may show adjusted values reflecting project-specific acoustic targets. The NC number (e.g. NC-25) is the authoritative performance criterion — the octave-band table is the implementation detail.

NC Curves — Standard Reference

10 dB20 dB30 dB40 dB50 dB60 dB63 Hz125 Hz250 Hz500 Hz1k Hz2k Hz4k Hz8k HzNC-12NC-18NC-25

Standard NC Curve Values (dB SPL)

FrequencyNC-12NC-18NC-25
63515460
125404452
250333745
500263140
1k222736
2k192434
4k172233
8k162132

Per-Room NC Budget

RoomNC TargetHVAC Max ContributionTransmitted MaxMargin
VO Live B304NC-12NC-10 (IDU-04 min fan)NC-105 dB
Control Room B311NC-18NC-15 (IDU-03 shared)NC-155 dB
Video Studio B312-1NC-18NC-15 (IDU-05)NC-155 dB
Editing Suite B312-2NC-25NC-22 (IDU-03 shared)NC-255 dB

Silencer Comparison

RunServesLengthAttenuationNC Max After
Run AVO Live (IDU-04)1,500mm40 dBNC-12
Run B (trunk)Control + Editing (IDU-03)1,000mm25 dBNC-18
Run B1 (branch)Control Room500mm15 dBNC-18
Run B2 (branch)Editing Suite300mm10 dBNC-25
Run CVideo Studio (IDU-05)1,000mm25 dBNC-18

Tangent Method Explanation

NC rating = highest NC curve touched by the measured spectrum.

Measure the sound pressure level at each octave band. Plot the values on the NC curve chart. The NC rating is determined by the highest NC curve that any measured value touches or exceeds. A single octave band exceeding the target curve defines the room's NC rating.