SSOT v3.7 · Contractor Detail Drawing · Acoustic Design Basis

Acoustic Ceiling Installation Detail

The suspended ceiling is part of the acoustic enclosure, not a decorative finish only. Tile support, perimeter movement, plenum barriers, and service cut-outs must follow these details so the 275 cm AFF ceiling line remains consistent in every room.

Slab to Slab
340 cm
Clear Height
275 cm AFF
Insulation
100 mm ProRox
Grid Module
600 mm

Drawing 1 — Vertical Cross-Section

340 cm slab to slab

Section from structural slab to floor. ProRox sits above the Rockfon Sonar E tiles over the full ceiling area, with the T-grid held at the 275 cm AFF line.

340 cm slab to slab 275 cm AFF Structural slab 37 cm plenum 100 mm ProRox above tiles T-grid + Rockfon Sonar E tile

Drawing 2 — Perimeter Wall Angle

Do not caulk tile to wall [AC]

The 25 × 25 mm aluminium wall angle supports the perimeter tile edge. A 5 mm movement gap remains between tile and wall and must not be sealed rigidly.

5 mm 25 mm 25 × 25 mm aluminium wall angle at 275 cm AFF 5 mm gap remains between tile edge and wall Do not caulk tile to wall — gap must remain [AC]

Drawing 3 — Plenum Barrier at Partition

Mandatory at all intersections [AC]

At every partition crossing, a 15 mm gypsum barrier lies flat over the tile plane for 600 mm each side and seals back to the partition face with Tremco.

600 mm each side [AC] Mandatory at ALL partition intersections 15 mm gypsum barrier on top of ceiling tiles Seal to partition face with Tremco both sides

Drawing 4 — T-Grid Layout Plan (Video Studio)

490 × 229 cm room

Main runners run parallel to the long axis. Cross tees fall at 600 mm spacing with dedicated openings reserved for IDU-05 and the lighting set-out.

IDU-05 cut-out Lighting cut-out 490 cm long axis 229 cm Main runners parallel to long axis Cross tees at 600 mm spacing Coordinate cut-outs before hanger set-out