Construction Guide

Lighting Infrastructure

Lighting fixtures, circuits, tally system, and cable separation. ALL fixtures tunable white 2700–3500K per B307 requirement.

Per-Room Fixture Schedule

RoomFixtureWattagePositionCircuitNotes
VO Live B3041× LED panel200W94cm from west wall / 149cm from north wallAV-02Tunable white 2700–3500K
Control Room B3111× LED panel40W98cm from north partition / 118cm from buffer spineAV-01Tunable white 2700–3500K
Video Studio B312-11× LED panel200W113cm from buffer spine / 247cm from east wallAV-03Tunable white 2700–3500K
Editing Suite B312-22× LED panels30W each140cm + 350cm from buffer spineAV-04Tunable white 2700–3500K
3× E-Light5W each, 4000KNear D1 / south wallAV-04Ambient + emergency egress
Global requirement: ALL fixtures must be tunable white 2700–3500K (B307 requirement). No exceptions.

Tally Light System

TALLY-01

Type
Red LED indicator
Position
Above D2, buffer spine (VO Live side)
Distance
52cm from spine

TALLY-02

Type
Red LED indicator
Position
Above D4 (Studio side)
ElementDetail
ControlSingle desk switch in Control Room controls both tally lights simultaneously
Signal cableLow-voltage 2-core from Control Room desk switch to both tally locations
ConduitSeparate conduit from audio and power cables

Dimming & Control

ParameterSpecification
Protocol0-10V or DALI
RangeAll main panels dimmable 0–100%
E-Light unitsOn/off only (not dimmable)

Cable Separation & Mounting Rules

RuleSpecification
Fixture mountingSurface mount or suspended — NO penetrations through acoustic ceiling [AC]
Lighting power conduitSeparate from audio signal conduit (300mm minimum)
Lighting cable typeStandard NMY or NYM — not required to be shielded
Shared conduitDO NOT share conduit with audio signal cables
Tally cableSeparate conduit from both audio and power
[AC] No ceiling penetrations for lighting fixtures. Surface mount or suspend from grid only. Penetrating the acoustic ceiling compromises the plenum barrier system.