SSOT v3.7 · Contractor Detail Drawing · Acoustic Design Basis
HVAC Silencer Installation Details
The duct silencers are the controlling acoustic elements in the HVAC system. Each run must keep the stated straight lengths, hanger spacing, and plenum insulation so the calculated attenuation is actually achieved on site [AC].
Run Count
5 runs
Longest
Run A · 1500 mm
Critical Branch
B2 crossover
Hangers
600 mm max spacing
Run A — VO Live
1500 mm · 40 dB · 1.5 m/sLongitudinal Cross-Section
Installation Position
Run B — IDU-03 Trunk
1000 mm · 25 dB · 2.0 m/sLongitudinal Cross-Section
Installation Position
Run B1 — Control Room Branch
500 mm · 15 dB · 2.0 m/sLongitudinal Cross-Section
Installation Position
Run B2 — Editing Branch
300 mm · 10 dB · 2.5 m/s maxLongitudinal Cross-Section
Installation Position
Run C — Video Studio
1000 mm · 25 dB · 2.0 m/sLongitudinal Cross-Section
Installation Position
IDU-03 Crossover Warning
[HP] Confirm branch separation before close-upIDU-03 serves Control Room AND Editing Suite. B1 (Control) and B2 (Editing) branch from a single trunk. A 15–20 dB silencer is required on the B2 crossover branch to prevent acoustic crosstalk between rooms [HP].