Buffer Spine

W5 — STC 55 — The acoustic heart of the facility

Overview

ParameterValue
NameBuffer Spine
West face X213.6 cm
East face X228.6 cm
Thickness15 cm
Wall typeW5 (STC 55, field 49–53)

Purpose

Acoustic separation between the west zone (VO Live + Control Room) and the east zone (Video Studio + Editing Suite).

HVAC routing — the ONLY permitted duct routing path between zones. All 5 silencer runs route through the buffer spine.

Circulation corridor via D2 (Control access, STC 45) and D4 (Studio/Editing access, STC 48).

This is not just a corridor wall — it is the core of the isolation strategy between the two most critical zones.

Wall Assembly W5

2×12.5mm gyp+GG (west face)
100mm steel studs + Rockwool infill
2×12.5mm gyp+GG (east face)

Lab STC: 55  |  Field STC: 49–53

HVAC Routing Through Buffer

RunLengthAttenuationServes
Run A1500mm40dBVO Live (IDU-04)
Run B1000mm25dBTrunk (splits to B1+B2)
Run B1500mm15dBControl branch (IDU-03)
Run B2300mm10dBEditing branch (IDU-03)
Run C1000mm25dBVideo Studio (IDU-05)

Main trunk B (1000mm/25dB) splits at a wye fitting into B1 (Control) and B2 (Editing). All 5 runs are shown separately — B1 and B2 are never collapsed into a single entry.

Column Detail [AC]

ParameterValue
ColumnCOL_W
Dimensions60 × 50 cm
Position(369.1, 140.6)
Air gap10mm [AC]
Detail requiredBox-out detail for duct routing around column

Door Access

DoorSTCLocationConnects
D245Buffer west faceControl Room access
D448Studio/Editing partitionStudio ↔ Editing

Buffer Footprint

West Zone VO Live + Control Buffer Spine East Zone Studio + Editing 15 cm 213.6 cm 228.6 cm D2 STC 45 D4 STC 48 UPGRADED COL_W W5 STC 55 N

Design Constraints [AC]

  • [AC] COL_W at (369.1, 140.6) — 10mm air gap must be maintained, box-out detail required
  • [AC] All 5 silencer runs must route through buffer spine — no alternative paths
  • [AC] Duct penetrations through W5 must be sealed with acoustic sealant
  • Buffer spine is the ONLY permitted HVAC routing path between zones