VO Live

B304 — Voiceover recording booth — The quietest room in the facility

Use Cases

Voiceover recording, vocal takes, singing, spoken word, podcasting, ADR (Automated Dialogue Replacement).

VO/singing hybrid mode: Manual acoustic curtain on north wall switches room character. Curtain CLOSED = VO mode (fully absorptive, RT60 0.20s, NC-12). Curtain OPEN = singing mode (vinyl floor ambience for vocalist, RT60 0.27s).

Requires NC-12 — the strictest noise criteria in the facility. This room is designed for the most noise-sensitive content where even subtle HVAC hum would be audible on recordings.

Room Data

ParameterValue
Room codeB304
Width (south)275 cm
Width (north)327 cm
Width (avg)301 cm
Depth176 cm
Area5.31 m²
Volume14.60 m³
Ceiling AFF275 cm [AC]
FlooringVinyl
NC targetNC-12
RT60 achieved0.20s (broadband)
Schroeder freq234 Hz
IDUIDU-04 (dedicated)

Floor Plan Position

VO Live occupies the northwest corner of the zone. Bounded by concrete walls on north (W1) and west (W2, diagonal), the buffer spine (W5) on the east, and the VO/Control partition (W6) on the south.

The observation window OW-1 (STC 50) is located in the south wall (W6), providing visual contact with the Control Room.

Room Footprint

327 cm (north) 275 cm (south) 176 cm diag. D3 OW-1 VO Live B304 · 5.31 m² N

Acoustic Treatment

ElementQtySpecification
Absorption panels8Rockwool RWA45 50mm, 1200×600mm, NRC 0.90
Bass traps4Rockwool RWA45 150mm, floor-to-ceiling, corners
QRD diffusers0
CeilingFullRockfon Sonar E, NRC 0.90
Motorized curtain1450g/m² velour, ceiling C-rail, dead/live positions

RT60 Analysis

BandTarget (s)Achieved (s)Status
125 Hz0.250.28✓ Pass
250 Hz0.220.23✓ Pass
500 Hz0.200.20✓ Pass
1 kHz0.180.19✓ Pass
2 kHz0.180.18✓ Pass
4 kHz0.180.17✓ Pass

Room Modes

ModeFrequency
Length (L)57.0 Hz
Width (W)97.3 Hz
Height (H)62.4 Hz
Schroeder234 Hz

Noise Criteria

Target: NC-12 — the quietest achievable rating for this room type.

Octave (Hz)631252505001k2k4k8k
NC-12 limit (dB)5140332622191716

Boundary Build-ups

WallTypeLab STCFieldAssembly
North (W1)Concrete6558–62300mm concrete + RSIC-1 + 50mm RW + 2×gyp
South (W6)Partition5347–51VO/Control partition (obs. window OW-1 here)
East (W5)Buffer spine5549–532×12.5mm gyp+GG + 100mm studs+RW + 2×12.5mm gyp+GG
West (W2)Diagonal concrete6558–62RSIC-V clips
CeilingRockfon Sonar ENRC 0.90, 275cm AFF
FloorFloatVinyl finish + 15cm Sylomer buildup

HVAC — Silencer Run A

ParameterValue
IDUIDU-04 (dedicated to VO Live only)
SilencerRun A: 1500mm, 40dB attenuation
Max velocity1.5 m/s
NC contribution maxNC-12
Risk R1IDU-04 self-noise must be verified at min fan speed [AC]
NC-12 Silencer Requirement
NC-12 demands ≤35 dB SPL at 4kHz octave band. IDU-04 supply and return ducts MUST have inline rectangular silencers (minimum 900mm length, 50mm Rockwool lining). Without silencers, IDU-04 alone will produce approximately NC-28 at the diffuser — 16 dB above target. This is non-negotiable for the NC-12 specification.

Design Constraints [AC]

  • [AC] NC-12 is achieved ONLY if IDU-04 runs at minimum fan speed — verify at commissioning
  • [AC] Perimeter gap 25mm → backing rod → Tremco MUST NOT be bridged
  • [AC] 4 bass traps required in corners — cannot be removed
  • Motorized curtain allows live (0.27s) vs dead (0.20s) mode switching
  • Observation window OW-1 (STC 50) is the weakest acoustic element in Wall W6 (STC 53)